<?xml version="1.0" standalone="yes"?>
<?xml-stylesheet type="text/xsl" href="..\..\XSLTemplates\NVSStyleSheet.xsl"?>
<Parameter>
<ParameterFamily>MDH</ParameterFamily>
<Syntax>
mhmedia separatorpulseinterval
</Syntax>
<AppliesTo>
<UnnumberedList>
<ListItem><TextApplies>Magnus_VLF</TextApplies></ListItem>
</UnnumberedList>
</AppliesTo>
<Description>
<DescriptionText><text>
This parameter configures the delay between the start of consecutive pulses of
the plenum separator while the picker is moving up after grabbing the plate.
The pulsing will occur between the picker motion counts specified
by the PickerMotionCountSeparatorOn and PickerMotionCountSeparatorOff parameters.
A pulse interval of zero means do not pulse the separator.  If the pulse duty
cycle is set higher than the pulse interval, the separator will not be pulsed.
</text></DescriptionText>
</Description>
<Availability>
<DescriptionText><text>
This parameter is available.
</text></DescriptionText>
</Availability>
<Default>
<UnnumberedList>
<li>Please issue the appropriate monitor command to determine this parameter's default value.</li>
</UnnumberedList>
</Default>
<Range>
<UnnumberedList>
<li>0 to 10000 [ms]</li>
</UnnumberedList>
</Range>
<LastModified>
21-Nov-2005
</LastModified>
<Notes>
<DescriptionText><text>
</text></DescriptionText>
</Notes>
<Access>
Normal
</Access>
<SeeAlso>
<UnnumberedList>
</UnnumberedList>
</SeeAlso>
<OtherLinks>
<li><Link><LinkAddress>..\..\ShowAllErrors.htm</LinkAddress><LinkTitle>Firmware 1 Error Index</LinkTitle></Link></li>
<li><Link><LinkAddress>..\..\ShowAllCommands.htm</LinkAddress><LinkTitle>Firmware 1 Command Index</LinkTitle></Link></li>
<li><Link><LinkAddress>..\..\ShowAllParameters.htm</LinkAddress><LinkTitle>Firmware 1 Parameter Index</LinkTitle></Link></li>
</OtherLinks>
<Updated>
Updated: Thu Jul 17 07:24:03 2008 PST
</Updated>
<Links>
</Links>
</Parameter>